When the SF6 concentration online monitoring system is used, the fan is started for a long time without any alarm display of the detection unit, and the fan cannot be shut down by pressing the

2014-01-05 ydlcb
  • The system has set the fan running time, clear the zero 00 time to judge;

  • Oxygen value decays below the fan starting point, but does not reach the alarm point; Adjust the internal potentiometer or instruct the user to lower the oxygen alarm point first.

  • The fan control relay is damaged and has become normally closed. Need to shut down test and replace;

  • Host control logic disorder, restart the machine;

  • The main board is defective and needs to be replaced and returned to Weavers' product workshop for further inspection.