Q&A
-
2017-03-05 What are the principles and characteristics of mea...
The principle of the detection tube method for measuring SF6 decomposition products is to use the measured gas to flow through the detection tube at a certain flow rate within a pre-set time, and chemical substances filled in the test tube of the tested gas Yui will undergo chemical reactions, and the content of decomposition products in the gas will be indicated by the length of the color change of the indicator in the detection tube. For example, the HF gas detection tube is filled with silica
Learn More -
2017-03-05 What are the characteristics of SF6 decomposition ...
Most of SF6 decomposition products are active, low in content and many kinds, so it is difficult to use one method for on-site quantitative detection. Some decomposes are very unstable and break down easily; Some of the decomposition is easily adsorbent, so the sample is collected into the sampling bottle, sent to the laboratory for analysis, the test results will reduce the concentration.
Learn More -
2017-02-20 What are the precautions for using SF6 gas density...
The SF6 gas density relay can accurately measure the SF6 gas density value only when the circuit breaker is out of operation and the temperature inside and outside the circuit breaker reaches the balance. When the circuit breaker is running, if the circuit breaker leaks SF6 gas, due to the effect of temperature rise, more SF6 gas should be leaked than when the circuit breaker exits the operation, so that the electrical contact of the density relay can be closed.
Learn More -
2017-02-18 What are the precautions for SF6 density relay dia...
(1) SF6 gas density relay can only compensate for the pressure change caused by the change of ambient temperature, but can not compensate for the load current through the conductor resistance and contact resistance when the equipment is running with electricity, all the electrical power consumed is converted into heat energy, so that the conductor heating causes the pressure change caused by the internal temperature rise of the equipment, especially in the case of high temperature and large load
Learn More -
2017-02-15 What are the hazards of sulfur hexafluoride (SF6) ...
SF6 gas has a century-old history, it is two French chemists Moissan and Lebeau synthetic artificial inert gas in 1900, around 1940, the United States military used it for the Manhattan Project (nuclear military). Since the mid-1960s, SF6 has been widely used as an insulating medium for high-voltage electrical equipment. SF6 gas-insulated switchgear covers a much smaller area than conventional open-type high-voltage distribution devices, and its operation is not affected by external meteorolo
Learn More -
2017-02-13 What are the emergency measures for SF6 device lea...
In case of a large amount of gas leakage due to the failure of indoor SF6 equipment, the staff should turn on the indoor ventilation device before leaving the accident site. Within 4 hours after the accident, any personnel entering the room must wear SF6 special protective clothing, SF6 special SF6 full cover, gloves, anti-static and anti-chemical safety shoes and SF6 positive pressure air breathing apparatus. After the accident, when cleaning the solid decomposition products inside the equipmen
Learn More